Sample Certificate of Analysis
40%
Sample COA. Contact Alliance Chemical with your lot number to request a lot-specific COA.
Sample specification reference for Inhibited Ethylene Glycol 40/60 with OAT-908 — Data Center Coolant. Source-record results are reference values, not measurements for your lot.
| Parameter | Specification | Source reference result | Test Method |
|---|---|---|---|
| Assay (ethylene glycol) | 39.0 - 41.0 % w/w | 40.0 % w/w | — |
| ASTM D1384 corrosion weight loss | copper 10 max; solder 30 max; brass 10 max; steel 10 max; cast iron 10 max; aluminum 30 max mg/specimen | Passes test | ASTM D1384 |
| Freeze point | -8.1 °F (-22.3 °C) max | -8.1 °F (-22.3 °C) | ASTM D1177 |
| Reserve alkalinity | 1.2 ml min. | 6.4 | — |
| Nitrite | 960 ppm min. | 960 ppm | — |
| Electrical conductivity @ 25 °C | 3500 µS/cm maximum | 2800 | ASTM D1125 |
| Silicates, phosphates, nitrites, borates, amines | None added — < 10 ppm each | 0.5 ppm | ICP-OES / ion chromatography |
| Foaming tendency (volume / break time) | 150 mL max / 5 s max | Passes test | ASTM D1881 |
| Sulfate (SO4) | 2.6 ppm max | 0.2 ppm | Turbidimetric, ACS procedure |
| Heavy metals (as Pb) | 0.41 ppm max | 0.04 ppm | ICP-OES / ACS heavy metals procedure |
| Identity (IR) | passes test | Passes test | — |
| Acidity as Acetic Acid | 0.002% max | 0.00012 % | — |
| Chloride (Cl) | 0.44 ppm max | 0.04 ppm | — |
| Diethylene Glycol | 0.02% max | 0.008 % | — |
| Iron (Fe) | 0.046 ppm max | 0.008 ppm | — |
| Residue after evaporation | 0.0021% max | 0.0004 % | — |
| Color | 10 max | 2.1 | — |
| Specific gravity (20 °C) | 1.048 - 1.058 | 1.053 | — |
| Composition | 40 % ethylene glycol in deionized water with the OAT-908 inhibitor package, by weight | Conforms | By formulation; confirmed by specific gravity |