Industrial chemicals · Taylor, TX
Certificate of Analysis

Sample Certificate of Analysis

Inhibited Ethylene Glycol 40/60 with OAT-908 — Data Center Coolant

40%

Category
Alcohols & Glycols (B)
CAS Number
107-21-1
Formula
C2H6O2
Revision
1.5

Sample COA. Contact Alliance Chemical with your lot number to request a lot-specific COA.

2D chemical structure of Inhibited Ethylene Glycol 40/60 with OAT-908 — Data Center Coolant
Structure · PubChem
Last reviewed 2026-07-17 by Andre Taki, DOT Hazmat Specialist.

COA · Answer summary

Sample specification reference for Inhibited Ethylene Glycol 40/60 with OAT-908 — Data Center Coolant. Source-record results are reference values, not measurements for your lot.

Assay specification
39.0 - 41.0 % w/w

Specifications

ParameterSpecificationSource reference resultTest Method
Assay (ethylene glycol)39.0 - 41.0 % w/w40.0 % w/w
ASTM D1384 corrosion weight losscopper 10 max; solder 30 max; brass 10 max; steel 10 max; cast iron 10 max; aluminum 30 max mg/specimenPasses testASTM D1384
Freeze point-8.1 °F (-22.3 °C) max-8.1 °F (-22.3 °C)ASTM D1177
Reserve alkalinity1.2 ml min.6.4
Nitrite960 ppm min.960 ppm
Electrical conductivity @ 25 °C3500 µS/cm maximum2800ASTM D1125
Silicates, phosphates, nitrites, borates, aminesNone added — < 10 ppm each0.5 ppmICP-OES / ion chromatography
Foaming tendency (volume / break time)150 mL max / 5 s maxPasses testASTM D1881
Sulfate (SO4)2.6 ppm max0.2 ppmTurbidimetric, ACS procedure
Heavy metals (as Pb)0.41 ppm max0.04 ppmICP-OES / ACS heavy metals procedure
Identity (IR)passes testPasses test
Acidity as Acetic Acid0.002% max0.00012 %
Chloride (Cl)0.44 ppm max0.04 ppm
Diethylene Glycol0.02% max0.008 %
Iron (Fe)0.046 ppm max0.008 ppm
Residue after evaporation0.0021% max0.0004 %
Color10 max2.1
Specific gravity (20 °C)1.048 - 1.0581.053
Composition40 % ethylene glycol in deionized water with the OAT-908 inhibitor package, by weightConformsBy formulation; confirmed by specific gravity

Specification limits and source-record results are reproduced from the current product reference used by the TDS. This sample is not an issued certificate and does not identify a tested lot. Contact Alliance Chemical with the product and lot number for lot-specific documentation.