Industrial chemicals · Taylor, TX
Certificate of Analysis

Sample Certificate of Analysis

Inhibited Ethylene Glycol 50/50 with OAT-908 — Data Center Coolant

50%

Category
Alcohols & Glycols (B)
CAS Number
107-21-1
Formula
C2H6O2
Revision
1.6

Sample COA. Contact Alliance Chemical with your lot number to request a lot-specific COA.

2D chemical structure of Inhibited Ethylene Glycol 50/50 with OAT-908 — Data Center Coolant
Structure · PubChem
Last reviewed 2026-07-17 by Andre Taki, DOT Hazmat Specialist.

COA · Answer summary

Sample specification reference for Inhibited Ethylene Glycol 50/50 with OAT-908 — Data Center Coolant. Source-record results are reference values, not measurements for your lot.

Assay specification
49.0 - 51.0 % w/w

Specifications

ParameterSpecificationSource reference resultTest Method
Assay (ethylene glycol)49.0 - 51.0 % w/w50.0 % w/w
ASTM D1384 corrosion weight losscopper 10 max; solder 30 max; brass 10 max; steel 10 max; cast iron 10 max; aluminum 30 max mg/specimenPasses testASTM D1384
Freeze point-28.9 °F (-33.8 °C) max-28.9 °F (-33.8 °C)ASTM D1177
Reserve alkalinity1.5 ml min.8.0
Nitrite1200 ppm min.1350 ppm
Electrical conductivity @ 25 °C4000 µS/cm maximum3200ASTM D1125
Silicates, phosphates, nitrites, borates, aminesNone added — < 10 ppm each0.5 ppmICP-OES / ion chromatography
Foaming tendency (volume / break time)150 mL max / 5 s maxPasses testASTM D1881
Sulfate (SO4)3 ppm max0.25 ppmTurbidimetric, ACS procedure
Heavy metals (as Pb)0.51 ppm max0.05 ppmICP-OES / ACS heavy metals procedure
Identity (IR)passes testPasses test
Acidity as Acetic Acid0.0025% max0.00015 %
Chloride (Cl)0.45 ppm max0.05 ppm
Diethylene Glycol0.025% max0.01 %
Iron (Fe)0.055 ppm max0.01 ppm
Residue after evaporation0.0026% max0.0005 %
Color10 max2.6
Specific gravity (20 °C)1.060 - 1.0701.065
Composition50 % ethylene glycol in deionized water with the OAT-908 inhibitor package, by weightConformsBy formulation; confirmed by specific gravity

Specification limits and source-record results are reproduced from the current product reference used by the TDS. This sample is not an issued certificate and does not identify a tested lot. Contact Alliance Chemical with the product and lot number for lot-specific documentation.