Industrial chemicals · Taylor, TX
Certificate of Analysis

Sample Certificate of Analysis

Inhibited Propylene Glycol 30/70 with OAT Inhibitor — Data Center Coolant

30%

Category
Alcohols & Glycols (B)
CAS Number
57-55-6
Formula
C3H8O2
Revision
1.4

Sample COA. Contact Alliance Chemical with your lot number to request a lot-specific COA.

2D chemical structure of Inhibited Propylene Glycol 30/70 with OAT Inhibitor — Data Center Coolant
Structure · PubChem
Last reviewed 2026-07-16 by Andre Taki, DOT Hazmat Specialist.

COA · Answer summary

Sample specification reference for Inhibited Propylene Glycol 30/70 with OAT Inhibitor — Data Center Coolant. Source-record results are reference values, not measurements for your lot.

Assay specification
29.0 - 31.0 % w/w

Specifications

ParameterSpecificationSource reference resultTest Method
Assay29.0 - 31.0 % w/w30.0 %
Propylene glycol concentration29.0 - 31.0 % w/w30.0 %
Inhibitor loading (OAT package)1.0–2.5 % OAT inhibitor package1.75 %Batch charge record / ion chromatography of carboxylates
Reserve alkalinity≥ 1.8 mL at 30 wt % propylene glycol2.2ASTM D1121
Silicate, phosphate, nitrite, nitrate, borate and amine contentNone detected (< 10 ppm each)0.3 ppmICP-OES / ion chromatography
Foaming tendencyVolume ≤ 150 mL; break time ≤ 5 sPasses testASTM D1881
Dipropylene glycol (DPG)0.15 wt% max0.075 wt%GC area % (ASTM E202)
Freeze point9.2 °F (-12.7 °C) max9.2 °F (-12.7 °C)ASTM D1177
Burst protection≤ -23 °C (-10 °F)-25 °C (-13 °F)Burst test
Acidity as Acetic Acid0.0015 % max0.00045 %
Chlorides as Cl0.58 ppm max0.12 ppm
Heavy Metals as Pb1.5 ppm max0.06 ppm
Iron0.31 ppm max0.03 ppm
ash0.0015% max0.00024 %
Color, Pt-Co10 APHA (maximum)1.5 APHA
AppearancePassPasses test
Suspended MatterPassPasses test
Composition30 % propylene glycol in deionized water with the OAT inhibitor package, by weightConformsBy formulation; confirmed by specific gravity

Specification limits and source-record results are reproduced from the current product reference used by the TDS. This sample is not an issued certificate and does not identify a tested lot. Contact Alliance Chemical with the product and lot number for lot-specific documentation.