Industrial chemicals · Taylor, TX
Certificate of Analysis

Sample Certificate of Analysis

Inhibited Propylene Glycol 40/60 with OAT Inhibitor — Data Center Coolant

40%

Category
Alcohols & Glycols (B)
CAS Number
57-55-6
Formula
C3H8O2
Revision
1.4

Sample COA. Contact Alliance Chemical with your lot number to request a lot-specific COA.

2D chemical structure of Inhibited Propylene Glycol 40/60 with OAT Inhibitor — Data Center Coolant
Structure · PubChem
Last reviewed 2026-07-16 by Andre Taki, DOT Hazmat Specialist.

COA · Answer summary

Sample specification reference for Inhibited Propylene Glycol 40/60 with OAT Inhibitor — Data Center Coolant. Source-record results are reference values, not measurements for your lot.

Assay specification
39.0 - 41.0 % w/w

Specifications

ParameterSpecificationSource reference resultTest Method
Assay39.0 - 41.0 % w/w40.0 %
Propylene glycol concentration39.0 - 41.0 % w/w40.0 %
Inhibitor loading (OAT package)1.0–2.5 % OAT inhibitor package1.75 %Batch charge record / ion chromatography of carboxylates
Reserve alkalinity≥ 2.4 mL at 40 wt % propylene glycol2.9ASTM D1121
Silicate, phosphate, nitrite, nitrate, borate and amine contentNone detected (< 10 ppm each)0.3 ppmICP-OES / ion chromatography
Foaming tendencyVolume ≤ 150 mL; break time ≤ 5 sPasses testASTM D1881
Dipropylene glycol (DPG)0.2 wt% max0.100 wt%GC area % (ASTM E202)
Freeze point-6.0 °F (-21.1 °C) max-6.0 °F (-21.1 °C)ASTM D1177
Burst protection≤ -38 °C (-37 °F)-40 °C (-40 °F)Burst test
Acidity as Acetic Acid0.002 % max0.0006 %
Chlorides as Cl0.64 ppm max0.16 ppm
Heavy Metals as Pb2 ppm max0.08 ppm
Iron0.41 ppm max0.04 ppm
ash0.002% max0.00032 %
Color, Pt-Co10 APHA (maximum)2 APHA
AppearancePassPasses test
Suspended MatterPassPasses test
Composition40 % propylene glycol in deionized water with the OAT inhibitor package, by weightConformsBy formulation; confirmed by specific gravity

Specification limits and source-record results are reproduced from the current product reference used by the TDS. This sample is not an issued certificate and does not identify a tested lot. Contact Alliance Chemical with the product and lot number for lot-specific documentation.