Technical Data Sheet
50%
| Test | Specification | Typical | Method | Source |
|---|---|---|---|---|
| Assay | 49.0 - 51.0 % w/w | 50.0 % | — | Interpreted |
| Propylene glycol concentration | 49.0 - 51.0 % w/w | 50.0 % | — | Interpreted |
| Inhibitor loading (OAT package) | 1.0–2.5 % OAT inhibitor package | 1.75 % | Batch charge record / ion chromatography of carboxylates | Interpreted |
| Reserve alkalinity | ≥ 3.0 mL at 50 wt % propylene glycol | 3.6 | ASTM D1121 | Interpreted |
| Silicate, phosphate, nitrite, nitrate, borate and amine content | None detected (< 10 ppm each) | 0.3 ppm | ICP-OES / ion chromatography | Interpreted |
| Foaming tendency | Volume ≤ 150 mL; break time ≤ 5 s | Passes test | ASTM D1881 | Interpreted |
| Dipropylene glycol (DPG) | 0.25 wt% max | 0.125 wt% | GC area % (ASTM E202) | Interpreted |
| Freeze point | -28.3 °F (-33.5 °C) max | -28.3 °F (-33.5 °C) | ASTM D1177 | Interpreted |
| Burst protection | ≤ -45 °C (-49 °F) | -47 °C (-53 °F) | Burst test | Interpreted |
| Acidity as Acetic Acid | 0.0025 % max | 0.00075 % | — | Interpreted |
| Chlorides as Cl | 0.7 ppm max | 0.2 ppm | — | Interpreted |
| Heavy Metals as Pb | 2.5 ppm max | 0.1 ppm | — | Interpreted |
| Iron | 0.51 ppm max | 0.05 ppm | — | Interpreted |
| ash | 0.0025% max | 0.0004 % | — | Interpreted |
| Suspended Matter | Pass | Passes test | — | Interpreted |
| Composition | 50 % propylene glycol in deionized water with the OAT inhibitor package, by weight | Conforms | By formulation; confirmed by specific gravity | Interpreted |
Specification values are guaranteed limits. Typical values are representative of production lots and are not guaranteed. Lot-specific certificates of analysis ship with every order.
| Grade | Concentration | Typical Assay | SKU | TDS |
|---|---|---|---|---|
| This grade — | 50% | — | current | current |
| — | 40% | — | SHOPIFY-7859432194090 | View TDS → |
| — | 35% | — | SHOPIFY-7990713942058 | View TDS → |
| — | 30% | — | SHOPIFY-7859429277738 | View TDS → |
| — | 25% | — | SHOPIFY-7990713909290 | View TDS → |
Typical assay shown is the rolling-window mean from the sibling product's most recent lots. Grade selection drives downstream end-use — verify the sibling grade matches your specification before substitution.
| Property | Value | Source |
|---|---|---|
| Appearance | Pass | Interpreted |
| Color | 10 APHA (maximum) | Interpreted |
| Odor | Mild, characteristic | Published reference |
| pH | 9-10.5 | Published reference |
| Specific Gravity (20 °C) | 1.046 (20 °C) | Published reference |
| Density | 1.046 g/mL at 20 °C | Published reference |
| Boiling Point | ~106 °C | Published reference |
| Melting Point | -33 °C (freeze / crystallization onset) | Published reference |
| Flash Point | Not flammable (aqueous solution) | Published reference |
| Solubility (water) | Miscible with water | Published reference |
Transport descriptions reflect 49 CFR 172.101 lookup at time of publication. Sourced data: ECHA CLP Annex VI for harmonised classifications, NIOSH Pocket Guide for REL/IDLH, OSHA Z-Tables for PEL. Always verify against the latest regulatory text before shipment-critical decisions.
One zipped download containing the TDS, SDS, latest lot COA (when available), and a fresh Letter of Continuing Guaranty for Inhibited Propylene Glycol 50/50 with OAT Inhibitor — Data Center Coolant. Every file included is SHA-256 hashed and listed in a manifest your QA team can audit.
Inhibited Propylene Glycol 50/50 with OAT Inhibitor — Data Center Coolant is a glycol-based heat-transfer and freeze-protection fluid. Concentration sets the freeze and burst protection; the inhibitor package sets how long the system stays protected from corrosion.
Verify concentration against the required freeze and burst protection, and confirm elastomer and metallurgy compatibility for the service temperature. Ethylene glycol is toxic by ingestion and must not be used where incidental food or potable contact is possible — specify a propylene glycol grade for those services.
For full hazard, PPE, and emergency response guidance, refer to the Safety Data Sheet (SDS) for this product. The SDS controls in all cases where guidance differs.
Not regulated for transport.
Confirm against shipping documents and carrier requirements before tender.
Last reviewed 2026-07-16 by Andre Taki, DOT Hazmat Specialist.
| Version | Date | Change | Trigger |
|---|---|---|---|
| 1.4 | 2026-09-09 | Canonical data updated: 1 field changed via the provenance/adjudication pipeline.
| canonical_change |
| 1.3 | 2026-07-24 | Canonical data updated: 1 field changed via the provenance/adjudication pipeline.
| canonical_change |
| 1.2 | 2026-07-22 | Canonical data updated: 1 field changed via the provenance/adjudication pipeline.
| canonical_change |
| 1.1 | 2026-07-16 | Canonical data re-verified: 10 fields updated against independent vendor SDSs, CLP Annex VI, 49 CFR, and OSHA HazCom 2024 (GHS classification, hazard/precautionary codes, signal word, physical properties as applicable).
| canonical_change |
| 1.0 | 2026-05-20 | Initial URL-first TDS published from canonical chemistry registry. | initial |
This Technical Data Sheet is provided for technical reference. The Safety Data Sheet (SDS) controls in all cases where guidance differs. Values reflect Alliance Chemical canonical data at time of generation; subsequent revisions are recorded in the Revision History above.